Defender Tank Protection

The Defender Tank Protection system is an air aspirating foam appliance designed to provide effective full-surface and rim seal fire suppression for storage tanks. A semi or fixed system appliance provides a quicker response time and less manpower than a portable, large volume delivery approach. The Defender requires less flow rate due to lower recommended application densities while exposing fewer personnel to a hazardous situation.

Please send inquiries with your tank diameter, type of tank and service for a defender package configured for your tank.

Patent Pending

Rim Seal Fire

Tank Diameter Application GPM
Water/Foam Required
GPM
Foam Concentrate 1%
Duration
in Minutes
Total Foam Concentrate
at 1%
100' 0.10 785 8 5 39
200' 0.12 3770 38 5 188
300' 0.12 8482 85 5 424

Full Surface Fire

Tank Diameter Application GPM
Water/Foam Required
GPM
Foam Concentrate 1%
Duration
in Minutes
Total Foam Concentrate
at 1%
100' 0.10 785 8 65 511
200' 0.12 3770 38 65 2450
300' 0.12 8482 85 65 5513

Type 3 Application

Tank Diameter Application GPM
Water/Foam Required
GPM
Foam Concentrate 1%
Duration
in Minutes
Total Foam Concentrate
at 1%
100' 0.16 1275 13 65 817
200' 0.18 5655 57 65 3676
300' 0.22 15551 156 65 10108

Video